HVTS tester perform DC high-voltage testing of power cables (IEC 60502-2), power cables accessories (IEC 61442) as well as AC high‑voltage testing of switchgear, reclosers, dielectric insulators, high-voltage dischargers (arresters), busbars and other dielectric materials with relatively low electric capacitance. Technical specifications Parameter HVTS-70/50 (L) DC AC 70 50 25 40 3 – 70 1 – 25 1 – 40 ± 3 (of reading) manual / 0.5 – 4 60 230 ± 23 50 ± 1 10 72 52 3 14 Max. output voltage, kV Max. output current,v mA Output voltage measuring range, kV Output current measuring range, mA Measurement error, %, max Voltage raising rate, kV/s Timer max. value, minutes Supply voltage, V Frequency, Hz HVU input overcurrent protection max. limit, A Voltage that triggers the overvoltage protection, kV, max Power consumption, kVA, max Control unit weight, kg, max HVU weight, kg, max Control unit dimensions, mm, max HVU dimensions, mm 35 349 × 256 × 240 360 × 500 × 310 Operating Conditions Air temperature, °С Relative humidity, % Atmospheric pressure, kPa (mm hg) -10 to +40 up to 85 at +25 °С 84.0 – 106.7 (630 – 800)